Detects the corrosiveness to copper of LPG. A polished copper strip is immersed in an LPG sample for one hour at 37.8°C (100°F) then removed and rated against an ASTM-IP Standard.
Comprises polished stainless steel vessel with two stainless steel needle valves, dip tube and 'O' ring sealed cap. 70 bar (1000psi) test pressure.
Certification: Pressure tested and supplied with a Works Test Certificate